Fire alarm inspection log.
What every fire alarm ITM entry must record under NFPA 72 (2025 edition) in the US and BS 5839-1:2017+A2:2023 in the UK. Weekly to annual frequency tables plus the 10-field log template used to demonstrate compliance to the AHJ and insurer.
A fire alarm inspection log is what proves the system was inspected, tested and maintained on schedule. NFPA 72 in the US and BS 5839-1 in the UK both require a written record of every inspection, test and impairment, kept in a form the Authority Having Jurisdiction and the insurer can inspect on demand. The tables below give the frequency schedule for each standard; the 10-field template lower on the page is what every log entry should contain.
Nothing on this page is legal advice. Verify obligations against the current standard adopted by your AHJ and a qualified competent servicing organisation.
NFPA 72 (US) ITM frequency
The schedule below is from NFPA 72 2025 Chapter 14 (Inspection, Testing, and Maintenance). Not every device type is listed at every frequency; refer to Chapter 14 Table 14.4.2.2 for the full device-by-device schedule.
| Frequency | Item | What to check |
|---|---|---|
| Weekly | Battery voltage under load | Standby battery voltage under load meets manufacturer spec; automatic trouble signal if failure detected |
| Monthly | Fire alarm control panel | Panel indicators show normal, no active troubles, disable or supervisory signals; visual check of all zone lamps |
| Quarterly | Detectors and initiating devices (sample) | Sample of manual pull stations, heat detectors, smoke detectors tested per Chapter 14 sampling table |
| Quarterly | Notification appliances (audible/visible) | Horns, strobes, speakers, chimes tested for correct sound level and synchronisation with mass notification if fitted |
| Semi-annual (2025) | Waterflow and supervisory devices | New in NFPA 72 2025: waterflow switch and tamper switch testing moved from quarterly to semi-annual |
| Annual | All initiating devices | Every heat detector, smoke detector, manual pull, duct detector, waterflow and supervisory switch tested per Chapter 14 table 14.4.2.2 |
| Annual | Sensitivity test (smoke detectors) | Every smoke detector tested against listed sensitivity range; readings recorded, drift-compensating detectors reset |
| Annual | Voice evacuation / mass notification | Full functional test of voice messaging paths and mass notification system if fitted; intelligibility per NFPA 72 Chapter 24 |
| Every 5 years | Sealed lead-acid battery | Battery replacement at manufacturer end-of-life, typically 5 years; capacity test after year 3 |
BS 5839-1 (UK) ITM frequency
The schedule below is from BS 5839-1:2017+A2:2023 Clauses 44 and 45. Weekly and monthly tasks are user-executable; 6-monthly and annual require a competent servicing organisation, typically BAFE SP203-1 or LPCB certified.
| Frequency | Item | What to check |
|---|---|---|
| Weekly | Manual call point test (rotating) | One MCP tested each week, rotating through the building so every MCP is tested within a defined cycle (Clause 44.2) |
| Monthly | Automatic system standby power | If standby generator fitted, monthly run-test with load transfer |
| 6-monthly | Every device (competent person) | Detectors, sounders, indicating devices, all fault indicators tested by a competent servicing organisation |
| Annual | System inspection and test | Full inspection to Clause 45.4, including sensitivity check on a sample of detectors and a written report |
| Every 10 years | Sensitivity of point-type smoke detectors | BS 5839-1 recommends detector replacement or laboratory sensitivity re-test at 10 years |
10 fields the log entry must record
Every log entry, whether weekly in-house or annual by a servicing organisation, needs the same 10 fields. Missing fields are what the AHJ auditor finds first.
Building and system identifier
Building address and unique system identifier (panel ID or install reference). Multi-building sites need one log per system, not one shared log.
Panel manufacturer, model, install date
Panel details recorded once at the front of the log; changes on upgrade or replacement.
Date and time of inspection
Every entry timestamped. Weekly entries need day-of-week consistency (typically same day each week for testing routines).
Inspector name and competence
For weekly and monthly in-house checks, the responsible person or delegate. For 6-monthly and annual, name of the servicing organisation and technician certification (BAFE SP203 in the UK, NICET Level II or III in the US).
Devices tested (or sampled)
List every device tested during this visit, or reference the sampling schedule showing which devices this visit covered.
Result per device
Pass, fail, or fail-take-out-of-service against each device. NFPA 72 Chapter 14 tables define acceptance criteria for each device type.
Battery test results
Standby battery voltage and load test result recorded. Under NFPA 72 the battery must support alarm load for the required duration (typically 24 hours standby + 5 min alarm).
Sensitivity readings (smoke detectors)
For annual sensitivity test, reading per detector recorded against listed range. Detectors outside range replaced or cleaned; drift-compensating detectors reset.
Impairments and repairs
Any device or zone out of service noted with start time, expected restoration, fire watch arrangement, and end time when restored. NFPA 72 2025 shortened the impairment notification window from 24 hours to 8 hours.
Signature and next inspection due
Inspector signs off. Next inspection date auto-calculated from the frequency table. Missed intervals highlighted for the responsible person.
Frequently asked
- What's the difference between NFPA 72 and BS 5839-1?
- NFPA 72 is the US National Fire Alarm and Signaling Code, published by NFPA and adopted in most US states. BS 5839-1 is the UK code of practice for fire detection and fire alarm systems for buildings other than dwellings. Both cover the same subject matter (design, install, commission, inspect, test, maintain) but with different frequency tables and different terminology. NFPA 72 is prescriptive on frequency; BS 5839-1 combines a fixed frequency schedule with more risk-based judgement by the servicing organisation.
- Can the weekly test be done by any staff member?
- Yes. Both NFPA 72 and BS 5839-1 allow the weekly test (typically a rotating manual call point activation) to be done by the responsible person or a delegate. The formal 6-monthly and annual service must be done by a competent servicing organisation, which in the UK usually means BAFE SP203-1 or LPCB certified, and in the US usually NICET Level II or higher for the technician and a licensed alarm contractor for the company.
- How long must the log be kept?
- NFPA 72 Chapter 14 requires records for the current inspection cycle plus 1 year, or as required by the AHJ (often 3 years). BS 5839-1 requires the log book to be kept for the life of the system. In practice most UK insurers ask for the previous 5 years on request, and post-Grenfell FSER 2022 duties for higher-rise residential effectively mean records are kept indefinitely as part of the building safety case.
- What are the biggest NFPA 72 2025 changes for inspection?
- Three changes stand out. First, the impairment notification window dropped from 24 hours to 8 hours; the AHJ, owner, and any monitoring station must be told within 8 hours of any impairment. Second, waterflow and supervisory device testing moved from quarterly to semi-annual (still annual functional test in most cases). Third, magnet testing of smoke detectors is now prohibited; sensitivity must be measured by listed test equipment. Existing systems are required to comply per Chapter 14.
- What's the difference between a functional test and a sensitivity test?
- A functional test proves the device activates the alarm signal when its trigger condition is met (smoke, heat, manual actuation, waterflow). A sensitivity test measures whether the device activates within its listed sensitivity range (typically expressed as %/foot obscuration for smoke detectors). NFPA 72 requires both: functional testing runs quarterly to annually depending on device type, sensitivity testing is annual for smoke detectors, and both must be recorded separately.
- Do I need a separate log for voice evacuation and mass notification?
- The log can be combined but the tests must be recorded distinctly. NFPA 72 Chapter 24 sets separate performance requirements for voice evacuation (intelligibility measured per STI or CIS methodology) and mass notification (message clarity, priority, and area coverage). BS 5839-8 covers voice alarm system testing in the UK. Both require an annual functional test with intelligibility measurement at designated listening positions.
Get the printable log
We are packaging the frequency tables and the 10-field log structure as a printable PDF plus an editable spreadsheet template, dual-standard for NFPA 72 (US) and BS 5839-1 (UK). Drop your work email and we will send it the moment it lands. No sales sequence.
Run the log on the phone
Hovermarks Inspection carries the NFPA 72 and BS 5839-1 schedules as scheduled forms. Weekly, monthly and quarterly tests run themselves; impairments log with automatic 8-hour AHJ notification reminders; the auditable pack per system is ready when the insurer or AHJ asks.
- NFPA 72 and BS 5839-1 schedules pre-loaded
- Impairment log with 8-hour reminder
- Sensitivity readings tracked device by device